HTS |
1 |
HygroFlex 1, 2 Analogue outputs No digital outputs 1 Probe connection RH values only 1 digital signal input No Third party probe input |
||
HTS |
2 |
HygroFlex 2, No Analogue outputs Digital outputs 2 Probe connections Full psychometric values available. Digital and analogue signal inputs Third party probe input |
||
HTS |
3 |
HygroFlex 3, 2 Analogue outputs Digital outputs 2 Probe connections Full psychometric values available. Analogue signal inputs Third party probe input |
||
1 |
12 to 35 VDU or 12 to 24 VAC Power | |||
2 |
90 to 250 VAC Power | |||
X |
No display | |||
D |
Display |
| Type | Polymer Sensor |
| Moisture Range: | |
| Relative Humidity | 0 - 100% |
| Dewpoint | -40 to +100oC |
| Accuracy: | +/- 1.5% +/-0.3oC |
| Repeatability: | Better than 0.5% RH / 0.1oC |
| Temperature Range: | Probe Dependant |
| Flow Rate; | Probe Dependant |
| Calibration: | NPL/NIST Traceable, recommended Yearly |
| Indicators: | LCD display, optional |
| Engineering Units | % RH, oC Dewpoint and Temperature, Wet-bulb, enthalpy, mixing ratio, water vapour pressure, saturation vapour pressure. |
| Controls: | 4 Push buttons, with display option |
| Outputs: | Analogue: upto 3 off 4 - 20 mA outputs, linearised to selected engineering units, option dependant |
| Digital: RS232, option dependant | |
| Power Supply: |
12 to 35VDC linear supply. 90 - 250VAC Mains, option dependant |
| Enclosure: | Thermo Plastic Casing, IP65 weather proofing |
| Pressure Range | Probe dependant |
| Electrical Connections: | Internal terminals |
| Mechanical Connections | Wall mounted electronics module |
| Warranty: | 1 Year |